(1)

Except as provided in Article 3.1.8.8., a fire damper having a fire-protection rating conforming to Sentence 3.1.8.4.(2) shall be installed in conformance with Article 3.1.8.10. in ducts or air-transfer openings that penetrate an assembly required to be a fire separation.

(2)

Except as provided in Article 3.1.8.9., a smoke damper or a combination smoke/ fire damper shall be installed in conformance with Article 3.1.8.11. in ducts or air-transfer openings that penetrate an assembly required to be a fire separation, where the fire separation

(a)

separates a public corridor,

(b)

contains an egress door referred to in Sentence 3.4.2.4.(2),

(d)

is installed to meet the requirements of Clause 3.3.1.7.(1)(b) or Sentence 3.3.3.5.(4). or 3.3.4.11.(4).