(1)
Except as permitted by Sentence (2), a library book storage room that is not normally accessible to the public shall be separated from the remainder of the building by a fire separation with a fire-resistance rating not less than 2 h if it
(a)
is more than 250 m
(b)
contains book stacks that
(i)
are more than 10 m high, or
(ii)
penetrate more than one floor assembly.
(2)
The fire separation required by Sentence (1) is not required if the book storage room is sprinklered.