(1)
Except as required by Sentence (2) and Articles 9.10.9.7. and 9.10.9.8. and as permitted by Article 9.10.9.9., penetrations of a required fire separation or a membrane forming part of an assembly required to be a fire separation shall be
(a)
sealed by a firestop that, when subjected to the fire test method in CAN/ULC-S115, “Standard Method of Fire Tests of Firestop Systems,” has an F rating not less than the required fire-resistance rating for the fire separation,
(b)
tightly fitted or cast in place, provided the penetrating item is made of steel, ferrous, copper, concrete or masonry, or
(2)
Penetrations of a firewall shall be sealed at the penetration by a firestop that, when subjected to the fire test method in “CAN/ULC-S115, “Standard Method of Fire Tests of Firestop Systems,” has an FT rating not less than the fire-resistance rating for the fire separation.