(1)
Except as permitted by Sentence (1.1) and except for doors serving single dwelling unit or a house with a secondary suite, exit doors that are required to swing shall swing in the direction of exit travel.
(a)
a room, suite or floor area having an occupant load of not more than 60 persons, or
(b)
as part of a means of egress from more than one floor area and the floor areas so served have a total occupant load of not more than 60 persons..
(2)
Doors that open onto a corridor or other facility that provides access to exit from a room or suite having an occupant load of more than 60 persons shall swing on the vertical axis in the direction of exit travel.
(3)
Doors that divide a corridor that is not wholly contained within a suite shall swing in the direction of exit travel.
(4)
Where a pair of doors is installed in a corridor that provides access to exit in both directions, the doors shall
(a)
swing in opposite directions, with the door on the right hand-side swinging in the direction of exit travel, or
(b)
swing in both directions.